Products

Tubular Batteries

Tubular Ultra Low Maintenance Battery is made using the special technology by which the active material is encapsulated in polyester tubes to prevent 'Shedding'. The electrode geometry facilities 'cyclic' deep discharges i.e. long repetitive power outages. They are recommended for back up power for UPS & Inverters where environmental conditions are tough and high ambient temperatures are common. Tubat Tobular proved to be most reliable source of back up power for Inverters and UPS operating under demanding conditions. These are capable of long hours of backup.


Applications Stored Power

  • UPS [Un-Interrupted Power Supply
  • Communication Equipments
  • High Frequency PWM
  • Solar Power Systems
  • Lighting
  • Domestic
  • Industrial
  • Inverter
  • Wind Mills
  • And Other Stationery Applications

Salient Features

  • Steady Output
  • Aquatrap Ventplug Ensures
  • Low Maintenance
  • No Acid Fumes
  • Eco Friendly
  • Low Antimony Allow
  • Large Top-Of-Plate Acid Head Room
  • Quick Recovery From Deep Discharge
  • Extra Backup Time

Initial Charging Instructions

  • Filling Gravity: 1.230 0.005 @ 27°C
  • Rest Period : 12
  • hours Charging Current: 0.10C Amps
  • Charging Duration: 48 hours (MINIMUM)
  • Final Gravity : 1.240 ~1.250 @ 27°C

Normal Charging Instructions

  • After a capacity discharge) Normal charging rate: 0.1 OC Amps Condition for fully charged state: (For both a & b) Charge till constancy in voltage and specify gravity reading for 3 consecutive hours and free gassing in all the cells.

Maintenance Instructions

  • Recharge battery after prolonged use. Keep battery top and terminal clean & dry Ensure good ventilation in the room
  • Toping with distilled water 2 to 3 times a year Wooden or plastic (No conductivity) planks should be used for placing the battery
Top